Chapter 12 of the Standard provides prescriptions about conductors and cables.
The Manufacturer shall select conductors so as to be suitable for the operating conditions and external influences.
Table 5 reports the minimal cross-sectional area of conductors.
The rating of cables depends on various factors such as insulation material (PVC or EPR) the number of conductors in a cable, design (sheathing), installation methods, grouping, and ambient temperature.
The Manufacturer shall install conductor cables, conductor busbars and collector ring assemblies in such a way that, during normal access to the machine, main protection is achieved by applying one of the following protection measures:
– protection by partial insulation of live parts, or where this is not practicable;
– protection by enclosures or barriers of at least IP2X or IPXXB.